PE new callback for exterior lights |
These lights don't come from LCP-E, the old panel, rather from main electrical room by the photovoltaics. They all key just fine by hand, so i suspect it is a scheduling or photocell problem Cts 8&10 key the parking lots just fine with 17+18 amps of flow. That is a problem, similar to the one we have in the gym - and the fault of circuit specifier/mapper. Continuous duty cts (more than three hours on) can only be rated for 80% of cb ampacity. In this case 80% of 20a is 16a. Out of range.
Bit that is not the issue.
If parking lot lites were out, they key fine by hand, so now I have to find the schedule or photocell.